CON-140 · Lesson 6 of 12 · 28 min

Fire separations, fire resistance and spatial separation

Codes do not try to prevent every fire. They aim to keep a fire small and local long enough for people to escape and for fire fighters to act. Two strategies do most of the work. Compartmentation divides the inside of a building into fire compartments with rated walls and floors, so that a fire in one apartment, store or corridor is held back from the rest of the building. Spatial separation limits the openings and combustible materials in exterior walls close to property lines, so that a fire in one building does not spread to the next. This lesson explains both, together with fire-resistance ratings, the testing behind them, the protection of openings and penetrations, and the site practices that keep ratings intact.

Construction managers have a large influence on whether a building's fire compartmentation works in reality. Most failures are not in the design but in installation: a missing firestop around a pipe, a fire damper not installed, a rated door with the wrong hardware, a gap at the top of a rated wall above the ceiling. These items are hidden after construction, so getting them right during the work is essential.

Fire-resistance ratings and testing

A fire-resistance rating is the time, in minutes or hours, that a building element or assembly withstands a standard fire test while continuing to perform its function. Walls, floors, roofs, columns and beams are tested in large furnaces following a standard time-temperature curve that rises to about 840 °C (1,550 °F) at one hour and about 1,010 °C (1,850 °F) at two hours. During the test the assembly must carry its design load if it is loadbearing, must not let flames or hot gases through, and must keep the temperature rise on the unexposed side below a set limit, typically an average of 140 °C (250 °F). Some tests also include a hose stream applied after the fire exposure to check that the assembly holds together.

In the US, fire-resistance tests follow ASTM E119 or the equivalent UL 263. Ratings for common assemblies are taken from listings such as the UL Product iQ directory (for example UL Design No. U305 for a wood stud wall), from the prescriptive assemblies in IBC Section 721, from calculated fire resistance under IBC Section 722, or from the Gypsum Association's Fire Resistance and Sound Control Design Manual.

A rated assembly is a complete system, not a list of materials. A one-hour wall listing specifies the stud size and spacing, the type and thickness of gypsum board, fastener type and spacing, joint treatment and any insulation. Using Type X gypsum board without the rest of the system does not produce a rated wall. Construction managers should require submittals to identify the listed assembly for every rated element and should check that site work matches it.

Fire barriers, fire partitions and smoke barriers

The IBC uses several kinds of rated element. Fire walls divide buildings, as Lesson 5 explained. Fire barriers are rated walls that separate occupancies, enclose exit stairs and shafts and create fire areas, and they must be continuous from the floor to the floor or roof deck above. Fire partitions are rated walls, usually 1 hour, separating dwelling units, sleeping units and corridors, and they may terminate at a rated ceiling in some cases. Horizontal assemblies are rated floors and roofs. Smoke barriers and smoke partitions resist the passage of smoke and are used mainly in institutional occupancies, where occupants are protected in place.

Typical IBC fire-resistance ratings. Exact requirements depend on occupancy, construction type and edition.
Element (typical)Typical rating
Exit stair enclosure, four stories or more2 hours
Exit stair enclosure, fewer than four stories1 hour
Shaft enclosure, four stories or more2 hours
Dwelling unit and sleeping unit separations1 hour (½ hour in Type IIB, IIIB and VB with sprinklers)
Corridors (where required)0 to 1 hour depending on occupancy, load and sprinklers
Occupancy separations (Table 508.4)1 to 4 hours, often reduced by 1 hour with sprinklers
Incidental use rooms such as large boiler rooms1 hour or sprinklers (Table 509.1)

Openings, closures and penetrations

A rated wall is only as good as its weakest opening. Doors, windows, ducts, pipes, cables and joints all create paths for fire and smoke, so codes require each to be protected to maintain the separation.

  • Doors in rated walls must be labeled fire door assemblies, including frame, hardware and glazing, with a rating usually less than the wall itself: for example a 45 min or ¾ h door in a 1 h wall and a 1.5 h door in a 2 h wall. They must be self-closing and latching, and many must close automatically on fire alarm.
  • Glazing in rated walls and doors must be a listed fire-protection or fire-resistance-rated glazing, limited in size and marked with its rating.
  • Ducts passing through rated assemblies need fire dampers, and some also need smoke dampers or combination fire and smoke dampers, installed according to their listing with access for inspection.
  • Pipes, conduits and cables passing through rated assemblies need listed firestop systems, chosen for the specific penetrating item, the size of the opening and the type of wall or floor.
  • Joints between rated walls and floors, and at the top of walls, need listed joint systems that accommodate movement while maintaining the rating.

Firestop systems in the US are tested to ASTM E814 or UL 1479 for penetrations and ASTM E1966 or UL 2079 for joints, giving F ratings (flame) and T ratings (temperature rise). The IBC generally requires an F rating at least equal to the assembly's rating, and a T rating for penetrations of rated floors in many cases. Fire dampers follow UL 555, smoke dampers UL 555S, and fire doors are tested to UL 10C and installed under NFPA 80.

Section through a rated gypsum board wall with three penetrations: a metal pipe sealed with intumescent sealant and mineral wool packing, a plastic pipe with an intumescent wrap collar, and a cable bundle in a sleeve with putty. A duct passes through further along, with a fire damper in a sleeve and an access door. Labels identify each listed system and the rated wall layers.
Every penetration through a rated assembly needs a listed system matched to the item, the opening and the wall or floor. Plastic pipes need intumescent collars or wraps because they melt and leave an open hole.

Firestopping is one of the most frequently failed inspections. Common problems include using a sealant not listed for the penetrating item, oversized holes, multiple items crowded into one opening, missing mineral wool packing, and penetrations added by later trades after firestopping is complete. Good practice is to assign firestopping to a single qualified contractor, require each trade to coordinate penetrations, label rated walls above ceilings, keep a log of penetrations with the listed system used, and inspect before ceilings are closed. Some owners require third-party firestop inspection.

Spatial separation and exterior walls

Fire can spread from building to building by radiant heat through windows and other openings in exterior walls, and by flames from openings igniting combustible cladding. Codes therefore limit the area of unprotected openings in an exterior wall, require minimum fire-resistance ratings and noncombustible cladding as the wall gets closer to the property line, and in some cases require sprinklers or protected openings.

The IBC handles exterior walls in Section 705. Fire separation distance is measured from the building face to the closest interior lot line, the center line of a street or public way, or an imaginary line between two buildings on the same lot. Table 705.5 sets the required fire-resistance rating of exterior walls by fire separation distance, occupancy and construction type. Table 705.8 limits the area of unprotected and protected openings in each story as a percentage of the exterior wall area of that story, according to the fire separation distance and whether the building is sprinklered. Exterior walls containing combustible materials, foam plastic insulation or metal composite panels have additional requirements, including testing to NFPA 285 for some walls in Types I to IV.

Plan view of two buildings on adjacent lots. An interior lot line runs between them. A dimension marks the fire separation distance from the left building's exterior wall to the lot line. The wall is shaded with window openings marked. A small table beside it shows that as fire separation distance increases, the permitted percentage of openings increases.
Fire separation distance is measured to the lot line, the center line of a street or an imaginary line between buildings on one lot.

Worked problem

Checking exterior wall openings

A sprinklered three-story office has an exterior wall facing an interior lot line at a fire separation distance of 12 ft. Each story of that wall is 100 ft long and 12 ft high (1,200 ft²). Table 705.8 permits 45 % unprotected openings for a sprinklered building at a distance of 10 to less than 15 ft. The architect has shown 600 ft² of windows on each story. Does the wall comply, and what are the options?

Show solution
  1. Permitted unprotected openings per story: 45 % × 1,200 ft² = 540 ft².
  2. Proposed: 600 ft², which exceeds 540 ft².
  3. The wall does not comply as drawn.
  4. Options: reduce windows to 540 ft² or less per story; use protected openings, such as listed fire-protection-rated glazing, which Table 705.8 allows in a larger percentage; or increase the fire separation distance by moving the building.

Answer: Not compliant: 600 ft² exceeds 540 ft² per story; reduce windows, use protected openings or increase the distance.

Exterior cladding has received close attention since the Grenfell Tower fire in London in 2017, which killed 72 people when flammable cladding spread fire up the outside of a residential tower. The IBC requires NFPA 285 testing for exterior walls with combustible components, such as foam plastic insulation, metal composite material, high-pressure laminates and water-resistive barriers, in buildings of Types I to IV of any height, with some exceptions. Construction managers should treat any substitution of cladding, insulation or water-resistive barrier on exterior walls as a code matter, because the tested assembly is only valid with the tested components.

Interior finishes and flame spread

Fire can also spread across the surfaces of walls and ceilings. Codes limit the flame spread and smoke development of interior finish materials, with stricter limits in exits, corridors and assembly and institutional occupancies. Paint, wallpaper, panelling, acoustic tiles and decorative materials can all be interior finishes for this purpose.

The IBC uses classes from the ASTM E84 (UL 723) tunnel test: Class A (flame spread index 0 to 25), Class B (26 to 75) and Class C (76 to 200), all with a smoke-developed index not over 450. Table 803.13 sets the required class by occupancy and location, with Class A or B required in exit enclosures and corridors in many occupancies, and reductions for sprinklered buildings. Textile wall coverings and expanded vinyl need room corner tests.

Keeping ratings intact during construction and renovation

Fire separations are built by many trades over many months, and each can damage them. Electricians cut holes for boxes, plumbers drill floors for pipes, mechanical contractors cut openings for ducts, and tenants later add cabling. On renovation projects, existing rated walls are often penetrated or partly removed. A construction manager can protect the ratings by:

  • Marking rated walls above ceilings with stencilled labels stating the rating, as many codes now require.
  • Requiring a penetration permit or log for any new opening in a rated assembly.
  • Scheduling firestop installation and inspection after all trades have finished penetrations but before ceilings close.
  • Checking that fire door hardware, closers and glazing match the labels and the door schedule.
  • Coordinating fire damper locations and access doors with the ceiling and wall finishes.
  • Photographing rated assemblies and firestops before concealment for the close-out record.

Worked problem

Selecting closures for a rated wall

A 2-hour fire barrier encloses an exit stair in a five-story building. Each floor has one door into the stair, and the designer wants a duct to pass through the stair enclosure wall. What closures are needed, and is the duct allowed?

Show solution
  1. Doors: a 1½-hour fire door assembly is required in a 2-hour fire barrier (IBC Table 716.1(2)), self-closing and latching, with limited glazing.
  2. Duct: IBC Section 1023.5 limits penetrations of interior exit stairway enclosures to equipment and ductwork necessary for the stair, such as pressurization, and electrical, sprinkler and standpipe items serving the stair. A duct serving other spaces must be rerouted.
  3. Any permitted penetration needs a listed firestop system with an F rating not less than 2 hours.
  4. Joints at the top of the wall need a listed joint system rated for 2 hours.

Answer: 1½-hour self-closing, latching door assemblies; reroute the duct because unrelated penetrations of exit enclosures are not allowed; listed 2-hour firestops and joint systems for permitted items.

Common mistakes

  • MistakeTreating Type X gypsum board as a rated assembly on its own.

    InsteadBuild to a complete listed or code-recognized assembly, including studs, fasteners, joints and insulation.

  • MistakeUsing any fire sealant at a penetration.

    InsteadUse the listed firestop system for the specific penetrating item, opening size and wall or floor.

  • MistakeStopping rated walls at the suspended ceiling.

    InsteadExtend fire barriers to the deck above; only some fire partitions may stop at a rated ceiling.

  • MistakeInstalling fire doors with non-listed hardware.

    InsteadMatch hardware, closers and glazing to the door label and the hardware schedule.

  • MistakeSubstituting cladding or insulation on exterior walls without review.

    InsteadTreat exterior wall substitutions as code matters requiring designer and, where needed, official approval.

Summary and key terms

  • Compartmentation and spatial separation keep fire local long enough for escape and fire fighting.
  • Fire-resistance ratings come from ASTM E119 or UL 263 tests, listings or IBC Sections 721 and 722.
  • A rated assembly is a complete system; materials alone do not provide a rating.
  • Fire barriers, fire partitions and horizontal assemblies separate occupancies, exits, shafts, units and corridors.
  • Doors, glazing, ducts, pipes, cables and joints in rated assemblies need listed closures, dampers and firestop systems.
  • Fire separation distance controls exterior wall ratings and opening percentages.
  • Most failures happen during installation; labeling, logs and inspections protect ratings.
Fire-resistance rating
Time an assembly withstands a standard fire test while performing its function.
Fire separation
NBC term; the IBC uses fire barriers, fire partitions and horizontal assemblies.
Fire compartment
An enclosed space separated by rated fire separations.
Closure
A device or assembly, such as a fire door, that protects an opening in a rated assembly.
Fire damper
A device in a duct that closes automatically to stop fire passing through a rated assembly.
Firestop system
A listed system that seals a penetration or joint in a rated assembly.
F rating
Time a firestop prevents flame passage in a test.
Limiting distance
NBC term; the IBC uses fire separation distance.
Unprotected opening
A window, door or other opening in an exterior wall without fire-rated protection.
Flame-spread rating
A measure of how fast flame spreads across a surface in a tunnel test.

Practice problems

Work each problem on paper first, then reveal the answer to check.

  1. What three criteria must a loadbearing wall meet in a fire-resistance test?

    Show answer

    Carry its load, prevent flame and hot gas passage, and limit temperature rise on the unexposed side.

  2. Why do plastic pipes need intumescent collars at rated penetrations?

    Show answer

    They melt in a fire, leaving an open hole; the collar expands to close it.

  3. What rating is required for a door in a 2-hour fire barrier?

    Show answer

    1½ hours.

  4. Why should firestopping be done by one contractor?

    Show answer

    To ensure consistent use of listed systems, clear responsibility and coordination of all penetrations.

  5. Permitted openings 25 %, wall 1,000 ft² per story: maximum openings per story?

    Show answer

    250 ft².

  6. How does sprinklering affect Table 705.8 percentages?

    Show answer

    It generally allows a larger percentage of openings.

  7. What did the Grenfell Tower fire show about exterior walls?

    Show answer

    Combustible cladding and insulation can spread fire rapidly up the outside of a building.

  8. Which test applies to exterior walls with combustible components in Types I to IV?

    Show answer

    NFPA 285.

  9. What interior finish class is typical in exit enclosures?

    Show answer

    Class A or B.

  10. Name three practices that protect fire separations during construction.

    Show answer

    Labeling rated walls, a penetration log and inspection of firestops before ceilings close.